Siemens SINAMICS S120 Commissioning Manual page 219

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

NOTICE
Damage to the device as a result of incorrectly selected rated current and/or maximum
current values
Incorrect rated current or maximum current data can destroy the motor!
• Check that the current values that have been entered are correct.
Note
If a power on or a warm restart is performed when the motor data identification is selected,
then the motor data identification request is lost. A requested motor data identification must
be reselected manually after powering up.
Note
As long as a rotating measurement has been selected and is running, you cannot perform
any upload, download, RAM to ROM or reset to the factory settings.
Precondition
● There is an online connection to the drive unit.
Assume master control
You require master control for the selected drive to perform the motor identification. Master
control has to be activated before the optimization measurements are started.
1. Click "Activate" at "Master control".
The "Activate master control" message window opens.
2. Carefully read the warning note and check the value of the monitoring time.
The monitoring time specifies the time that the connection between the PC and drive is
cyclically monitored. The minimum value is 1000 ms.
3. Click "Continue" to confirm the monitoring time.
The message window closes. The "Stationary/rotating measurement" screen form is then
active.
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
Commissioning
4.10 Commissioning a drive