Interconnection for "Enable output-side breaker"
Figure 8-37
Interconnection for "Enable output-side breaker"
The breaker must also trip in the event of a converter fault. This is achieved using the
specified interconnection.
To activate the interconnection, parameterization (in the expert list) must be carried out as
follows (in this example, it has been assumed that the drive is called "Drive_1" in the project
navigator):
Table 8- 52
Parameterization for the interconnection for "Enable output-side breaker"
Parameterization
(TM31) p4030 = (Drive_1) r2139.3
(TM31) p4048.0 = 1 = inverted
Cabinet Modules
Manual, 03/2013, A5E03263538A
Description
The "Fault active" drive signal is output at digital output 0 (DO 0) of the
TM31.
Digital output 0 (DO 0) is inverted.
8.31 L34, output-side circuit breaker
Options
481