Options
8.9 K46, Sensor Module Cabinet-Mounted SMC10
Use shielded temperature sensor cables
Cables to connect temperature sensors must always be installed with shielding. The cable
shield must be connected to the ground potential at both ends over a large surface area.
Connecting cables that are routed together with the motor cable must be twisted in pairs
and shielded separately.
8.9.3
Interfaces
Overview
Figure 8-12
388
CAUTION
Interface overview for the SMC10
Cabinet Modules
Manual, 03/2013, A5E03263538A