Risk of electric shock!
Only temperature sensors that meet the safety isolation specifications stipulated in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp". If safe electrical
separation cannot be guaranteed (for linear motors or third-party motors, for example), a
Sensor Module External (SME120 or SME125) must be used.
Failure to observe these instructions can result in electric shock!
Note
Connectable sensor
The following sensors can be connected to the temperature sensor connection:
KTY84-1C130 / PTC / PT100
NOTICE
Use shielded cables
The temperature sensor connection must be shielded. The shielding must be attached to
the shield support of the Motor Module.
Note
KTY temperature sensor connected with the correct polarity
The KTY temperature sensor must be connected with the correct polarity.
If the polarity is reversed, the sensor will not be able to detect if the motor overheats.
Note
Safety Integrated Function Manual
Detailed and comprehensive instructions and information for the Safety Integrated functions
can be found in the associated Function Manual. This manual is available as additional
documentation on the customer DVD supplied with the device.
Note
EP terminals only for Safety Integrated Basic Functions
The function of the EP terminals is only available when Safety Integrated Basic Functions
are enabled.