G56, Contactor Monitoring; K01 To K05, Safety License For 1 To 5 Axes - Siemens SINAMICS S120 Manual

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options

8.6 G56, contactor monitoring

8.6
G56, contactor monitoring
Availability of option
This option is available for the following S120 cabinet modules:
● Basic Line Modules
● Smart Line Modules
● Active Line Modules
Description
The protective monitoring option is used for monitoring the pre-charging and bypass
contactors of the Line Modules.
The connecting cable from the contactors to the Control Interface Module is factory-installed.
Activation
The monitoring is activated using the following parameters:
● p0255.0 = monitoring time for the pre-charging contactor (factory setting = 0, max. 6500 ms)
● p0255.1 = monitoring time for the bypass contactor (factory setting = 0, max. 6500 ms)
Fault messages
● F30060 (A) pre-charging contactor status monitoring
● F30061 (A) bypass contactor status monitoring
8.7

K01 to K05, safety license for 1 to 5 axes

Availability of option
This option is available for the following S120 Cabinet Modules:
● Booksize Cabinet Kits
● Chassis format Motor Modules
382
Cabinet Modules
Manual, 03/2013, A5E03263538A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents