4.1

Power Supply Connections

86
should be connected to any of the two functional earth terminal screws positioned on
the upper and lower-middle parts of the frontal panel of the equipment through short
pigtails. Recommended lug terminal to the pigtail end connection.
The unit can be powered from DC or AC power within the limits specified in the
Technical Specifications Chapter.
All power connections should use insulated flameproof screened/shielded cable with a
2.0 mm2 cross section, 70° C (158 °F) thermal class, and 750 V insulation voltages.
To reduce the risk of electrical shock, pre-insulated tubular pin terminals should be used
on the ends of the power connections.
Pre-insulated tubular pin terminals
The pin terminals should be completely inserted into the connector supplied with the
unit so that no metallic parts are exposed, according to the picture below.
Supplied connector assembly
For optimal electromagnetic compatibility, ground the unit by using a
screened/shielded cable with insulated flexible wires of 2.0 mm² cross section
connected to the rear panel of the device using the protective earth screw.