1.5
Dry-contact Relay Outputs
DR60-TM-EN-2A
Bitrate
Databits
Stopbits
Parity
Connector
Isolation Level
Description
Switching Voltage
Permissible current continuous
Maximum voltage
Making Capacity
Breaking Capacity
Dropout time
Burden
Withstand voltages across open
contacts
Permissible short time value for 1s
1200, 2400, 4800, 9600, 19200, 38400 bps
7 or 8
1 or 2
None, even, odd
DB9 (female), standard DTE
1.44 KVdc
IN SERVICE contact
Dry contact relay, normally closed
250 V ( AC and DC)
5 A
300 (AC and DC)
15 A, 4 sec
40W Resistive, 25 W/VA L/R = 50
< 5 ms
~50mA @12V [600mW]
1000V rms
30A
DR60
109