Siemens SINAMICS S120 Function Manual page 209

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

● If the "Safe Stop 1" of the Basic Functions is not selected within the tolerance time in two
channels, this is detected by the cross-check, and fault F01611 (STOP F) is output. After
the set "SI Safe Stop 1 delay time" (p9652), the pulses are suppressed.
Note
In order that the drive can brake down to a standstill even when selected through one
channel, the time in p9652 must be shorter than the sum of the parameters for the data
cross-check (p9650 and p9658). Otherwise, the drive will coast down after the time
p9650 + p9658 has elapsed.
Further notes for setting the discrepancy time (also see the following diagram "Discrepancy
time") are provided in the "SINAMICS S120/S150 List Manual" for the following message:
● F01611 (Basic Functions)
● C01770 (Extended/Advanced Functions)
T
S
T
D
T
R
Figure 5-3
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p9650
• p9652
• p9658
• p10002
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
5.2 Control signals by way of terminals on the Control Unit and Motor / Power Module
Switching interval
Discrepancy time
Response time
Discrepancy time
SI SGE switchover discrepancy time (Control Unit)
SI Safe Stop 1 delay time (Control Unit)
SI transition time STOP F to STOP A (Control Unit)
SI Motion F-DI switchover discrepancy time (CPU 1)
Control of the safety functions
207