Siemens 6DR50 Series Operating Instructions Manual page 39

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

1. Install the clamping pieces
socket cap screws
2. Slide the pick-up bracket
Figure 4-1
3. Set the necessary length.
4. Tighten the screws
5. Fix the pre-installed carrier pin
washer
Figure 4-2
6. Set the stroke value. Use the stroke value specified on the nameplate of the actuator for
this purpose. If none of the values on the lever scale matches the stroke value of the
actuator, select the next higher value on the scale. Position the pin center
corresponding value of the scale. If you need the value of actuator travel after
initialization in mm: ensure that the configured stroke value matches the value of the
"3.YWAY" parameter.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
on the actuator spindle. Use spring lock washers
for this purpose.
into the milled recesses of the clamping pieces
Pick-up bracket
so that you can still shift the pick-up bracket
and hexagon nut
Lever with carrier pin
to the lever
. Use the flat washer
for this purpose.
Installing/mounting
4.2 Mounting the linear actuator
.
.
, spring lock
on the
and
37