Parameterizing/addressing
9.3 Parameter overview
Parameter
Function
41.YCUP
Upper value for tight closing
42.BIN1
Function of binary input 1
2)
43.BIN2
Function of binary input 2
2)
44.AFCT
Alarm function
3)
45.A1
Response threshold, alarm 1
46.A2
Response threshold, alarm 2
Function for fault message output
47.
FCT
3)
150
None
Message only
Block configuration
Block configuration and manual
Drive valve to position YE
Drive valve to position YA
Block movement
Partial stroke test
None
Message only
Drive valve to position YE
Drive valve to position YA
Block movement
Partial stroke test
None
A1 = Min, A2 = Max
A1 = Min, A2 = Min
A1 = Max, A2 = Max
Fault
Fault + not automatic
4)
Parameter values
0.0 ... 99.5 ... 100.0
Normally open
OFF
on
bLoc1
bLoc2
uP
doWn
StoP
PSt
Normally open
OFF
on
uP
doWn
StoP
PSt
Normal
OFF
0.0 ... 10.0 ... 100.0
0.0 ... 90.0 ... 100.0
Normal
Operating Instructions, 09/2014, A5E00074631-12
Unit
%
Normally closed
-on
-uP
-doWn
-StoP
-PSt
Normally closed
-on
-uP
-doWn
-StoP
-PSt
Inverted
%
%
Inverted
SIPART PS2 with and without HART