2.4 Minimum fault current
The minimum fault current I fmin on a protected transmission line is the current of the phase to
earth fault on the nearest remote terminal.
A s/s
To calculate I fmin , zero sequence earth fault current (I o ), positive sequence earth fault current (I 1 )
and negative earth fault current (I 2 ) are calculated as follows:
I 0 = I 1 = I 2 = (Source voltage)/{(Back impedance of A s/s)
= (150kV/ 3 )/{(0.94 × 75) + 16.8 × (0.4970
= 822.28A
So,
I fmin = I 0 + I 1 + I 2 = 3 × 822.28 = 2.47kA
*Note:
Assuming that positive sequence impedance = negative sequence impedance.
2.5 Scheme setting
Element
CRSCM
DISCR
DEFCR
ZS-C
ZG-C
CHSEL
BOSW
ZONESEL
ECHO
WKIT
CH-DEF
PSB-Z1
PSB-Z2
PSB-Z3
PSB-CR
PSB-ZR
Line length: 16.8km
GRL100
+ (Transmission line zero sequence impedance)
+ (Transmission line positive sequence impedance) × 2*}
+ 2 × 16.8 × (0.0197