Toshiba GRL100-701B Instruction Manual page 398

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

Overvoltage Protection
Phase-to-phase element (OVS)
st
nd
1
, 2
Overvoltage thresholds:
st
Delay type (1
threshold only):
IDMTL Time Multiplier Setting TMS:
DTL delay:
Dropout / Pickup ratio:
Phase-to-earth element (OVG)
st
nd
1
, 2
Overvoltage thresholds:
st
Delay type (1
threshold only):
IDMTL Time Multiplier Setting TMS:
DTL delay:
Dropout / Pickup ratio:
Undervoltage Protection
Phase-to-phase element (UVS)
st
nd
1
, 2
Undervoltage thresholds:
st
Delay type (1
threshold only):
IDMTL Time Multiplier Setting TMS:
DTL delay:
Undervoltage block threshold:
Phase-to-earth element (UVG)
st
nd
1
, 2
Undervoltage thresholds:
st
Delay type (1
threshold only):
IDMTL Time Multiplier Setting TMS:
DTL delay:
Undervoltage block threshold:
Thermal Overload Protection
Thermal setting (THM = k.I
FLC
Time constant ( τ )
Thermal alarm
Pre-load current setting
Switch-on-to-fault and Stub Protection
Overcurrent
Broken Conductor Detection
Broken conductor threshold (I
DTL delay:
Breaker Failure (BF) Protection
Overcurrent element
Reset
BF timer for retry-trip of failed circuit breaker
BF timer for adjacent circuit breaker tripping
Operating time of overcurrent element
Resetting time of overcurrent element
OFF, 5.0 – 150.0V in 0.1V steps
DTL, IDMTL
0.05 - 100.00 in 0.01 steps
Inst, 0.01 - 300.00s in 0.01s steps
10 to 98% in 1% steps
OFF, 5.0 – 150.0V in 0.1V steps
DTL, IDMTL
0.05 - 100.00 in 0.01 steps
Inst, 0.01 - 300.00s in 0.01s steps
10 to 98% in 1% steps
OFF, 5.0 – 150.0V in 0.1V steps
DTL, IDMTL
0.05 - 100.00 in 0.01 steps
Inst, 0.01 - 300.00s in 0.01s steps
5.0 to 20.0V in 1V steps
OFF, 5.0 – 150.0V in 0.1V steps
DTL, IDMTL
0.05 - 100.00 in 0.01 steps
Inst, 0.01 - 300.00s in 0.01s steps
5.0 to 20.0V in 1V steps
)
OFF, 0.40 – 2.00A in 0.01A steps (1A rating)
OFF, 2.0 – 10.0A in 0.1A steps (5A rating)
0.5 – 300.0mins in 0.1min steps
OFF, 50% to 99% in 1% steps
0.00 – 1.00A in 0.01A steps (1A rating)
0.0 – 5.0A in 0.1A steps (5A rating)
0.4 to 3.0A in 0.1A steps (1A relay)
2.0 to 15.0A in 0.1A steps (5A relay)
/I
):
OFF, 0.10 - 1.00 in 0.01 steps
2
1
0.00 to 300.00s in 0.01s steps
0.1 to 2.0A in 0.1A steps (1A relay)
0.5 to 10.0A in 0.1A steps (5A relay)
less than 80% of operating value
50 to 500ms in 1ms steps
50 to 500ms in 1ms steps
less than 20ms at 50Hz or 17ms at 60Hz
less than 15ms at 50Hz or 13ms at 60Hz
 397 
6 F 2 S 0 8 5 0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl100-702bGrl100-711bGrl100-712b

Table of Contents