3 Functions
START
P0340 = 1
Additional Cata-
log and/or ECD
data known ?
no
yes
P0341 = ...
P0342 = ...
P0344 = ...
ECD data
known ?
no
yes
P0340 = 4
P0350 = ...
P0354 = ...
P0356 = ...
P0358 = ...
P0360 = ...
P0340 = 3
END
90
Calculation of motor parameters
This parameter is required during commissioning in order to optimize the
operating behavior of the drive inverter. For the complete parameterization
(P0340 = 1), in addition to the motor / control parameters, parameters are pre-
assigned which refer to the rated motor data (e.g. torque limits and reference
quantities for interface signals). A list of the parameters, which are calculated,
depending on the setting of P0340, are included in the parameter list.
0
No calculation
1
Complete parameterization
2
Calculation of equivalent circuit data
3
Calculation of V/f and Vector control data
4
Calculation of controller settings only
2
Motor inertia [kgm
]
Total/motor inertia ratio
Motor weight (entered in kg)
Calculation of motor parameters
4
Calculates the controller setting (refer to parameter P0340)
Stator resistance (line-to-line) (entered in Ω )
Stator resistance in Ω of the motor which is connected (from line-to-line). This
parameter value also includes the cable resistance.
Rotor resistance (entered in Ω )
Defines the rotor resistance of the motor equivalent diagram (phase value).
Stator leakage inductance (entered in mH)
Defines the stator leakage inductance of the motor equivalent diagram
(phase value).
Rotor leakage inductance (entered in mH)
Defines the rotor leakage inductance of the motor equivalent diagram
(phase value).
Main inductance (entered in mH)
Defines the main (magnetizing) inductance of the motor equivalent diagram
(phase value).
Calculation of motor parameters
3
Calculation of V/f and Vector control
All of the parameters, dependent on the ECD data are calculated and, in
addition, the controller settings (P0340 = 4).
The motor parameters have been calculated and it is now possible to return to
the additional parameterization in the Section 3.5.7 "Commissioning the
application".
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Issue 10/06
Factory setting
0
FU-spez.
FU-spez.
FU-spez.
0
FU-spez.
FU-spez.
FU-spez.
FU-spez.
FU-spez.
0

Hide quick links: