3 Functions
3.5.7.9

Fixed frequency (FF)

Fixed frequency 1
P1001 = ...
Can be directly selected via DIN1
(P0701 = 15, 16)
Fixed frequency 2
P1002 = ...
Can be directly selected via DIN2
(P0702 = 15, 16)
Fixed frequency 3
P1003 = ...
Can be directly selected via DIN3
(P0703 = 15, 16)
Fixed frequency 4
P1004 = ...
Can be directly selected via DIN4
(P0704 = 15, 16)
P1005 = ...
Fixed frequency 5
Can be directly selected via DIN5
(P0705 = 15, 16)
Fixed frequency 6
P1006 = ...
Can be directly selected via DIN6
(P0706 = 15, 16)
P1007 = ...
Fixed frequency 7
P1008 = ...
Fixed frequency 8
P1009 = ...
Fixed frequency 9
Fixed frequency 10
P1010 = ...
Fixed frequency 11
P1011 = ...
Fixed frequency 12
P1012 = ...
Fixed frequency 13
P1013 = ...
Fixed frequency 14
P1014 = ...
Fixed frequency 15
P1015 = ...
Fixed frequency code - Bit 0
P1016 = ...
Defines the selection method for fixed
frequencies.
P1017 = ...
Fixed frequency code - Bit 1
Fixed frequency code - Bit 2
P1018 = ...
Fixed frequency code - Bit 3
P1019 = ...
Fixed frequency code - Bit 4
P1025 = ...
Fixed frequency code - Bit 5
P1027 = ...
104
0.00 Hz
5.00 Hz
10.00 Hz
When defining the function of the digital inputs
15.00 Hz
(P0701 to P0703), three different types can be
selected for fixed frequencies:
15 = Direct selection (binary-coded)
In this particular mode, the appropriate
20.00 Hz
digital input always selects the associated
fixed frequency, e.g.:
Digital input 3 = selects fixed frequency 3.
If several inputs are simultaneously active,
25.00 Hz
then these are summed. An ON command is
additionally required.
16 = Direct selection + ON command
(binary-coded + On / Off1)
30.00 Hz
In this mode, the fixed frequencies are
selected as for 15, however these are
35.00 Hz
combined with an ON command.
17 = Binary coded selection + ON command
40.00 Hz
(BCD-coded + On/ Off1)
The BCD-coded operating mode is effective for
45.00 Hz
digital inputs 1 to 3.
50.00 Hz
55.00 Hz
60.00 Hz
65.00 Hz
65.00 Hz
1
1
Direct selection
2
Direct selection + ON command
3
Binary coded selection + ON command
NOTE
1
For settings 2 and 3, all parameters P1016 to
P1019 must be set to the selected value so that
1
the drive inverter accepts the ON command.
1
1
1
Direct selection
2
Direct selection + ON command
1
MICROMASTER 440
Issue 10/06
Operating Instructions
6SE6400-5AW00-0BP0