Issue 10/06
Contrary to "Direct selection + ON command", the ON command is only active if
the setting for the first 4 binary inputs is set to "Binary-coded selection + ON
command" or P0701 = P0702 = P0703 = P0704 = 17. The following is obtained
analog to the above example:
a) Standard method
b) BICO method
P0701 = 17 or P0701 = 99, P1020 = 722.0, P1016 = 3
P0702 = 17 or P0702 = 99, P1021 = 722.1, P1017 = 3
DIN1
DIN2
Fig. 3-50
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
P1020
r0722.0
0
P1021
r0722.1
0
-650.00 ... 650.00 [Hz]
Example for selecting FF1 via DIN1 and FF2 via DIN2 using the binary-coded
method
P0701 = 17
P0701 = 99, P1020 = 722.0, P1016 = 3
1
2,3
1
...
2,3
Festf requenz 1
0 0 0
P1001.D ( 0.00)
.
.
.
Festf requenz 15
1 1 1
-650.00 ... 650.00
[Hz]
P1015.D ( 65.00)
3 Functions
1
.
CO: Ist-
Festf req.
.
r1024
.
1
169