Closed-loop PID control

MICROMASTER has a technology controller (PID controller, enabled using
P2200); this can be used to execute basic, higher-level control functions.
The technological setpoints and actual values can be entered via the PID
motorized potentiometer (PID-MOP), PID fixed setpoint (PID-FF), analog inputs
(ADC, ADC2) or via serial interfaces (USS on BOP link, USS on COM link, CB on
COM link) (refer to the example). The appropriate parameterization of the BICO
parameter defines which setpoints or actual values are to be used (refer to Fig.
3-54).
PID
MOP
ADC
PID
FF
USS
BOP link
USS
COM link
CB
COM link
ADC2
Fig. 3-54
Important parameter settings for the setpoint and actual value sources of the
closed-loop PID control:
Parameter
P2200
P2251
P2253
P2264
NOTICE
Changes in parameter P2200 take effect only after a fresh ON command.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
P2254
PID
PID
P2253
SUM
RFG
PID
P2264
PT1
P2200
Structure of the technological controller (PID controller)
Parameter text
BI: Enable PID controller
PID mode
CI: PID setpoint
CI: PID feedback
PID
PID
PT1
PID
Output
PID
PID
SCL
Setting
Meaning
1.0
PID controller always active
722.x
Digital input x
0
PID as setpoint
2224
Fixed PID setpoint (PID-FF)
2250
PID-MOP
755.0
Analog input 1
2015.1
USS on BOP link
2019.1
USS on COM link
2050.1
CB on COM link
755.0
Analog input 1
755.1
Analog input 2
3 Functions
0
Motor
control
1
&
P2251
175