Figure 5: Rear And Front Views Of The Ra331, Respectively - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 3 – Hardware Design
2.2.1
Main Features
2.2.2
Components
RPV311-TM-EN-7
Up to 8 analog inputs (voltage, current, DC transducers, probes);
Up to 32 digital inputs;
16-bit analog-to-digital converters, 256 points-per-cycle sampling rate;
Frequency response of DC to 3.0 kHz;
Fiber-optic interface to connect to the processing module;
Up to 2 km fiber-optic links;
Front panel mounting or internal panel mounting.
Figure 5
shows all the components of the RA331 module.

Figure 5: Rear and front views of the RA331, respectively

A
AC or DC power input.
B
Mains and Ready back panel indicators: The Mains is lit when the module is
powered. Ready indicator lights up after the module self-test is completed.
C
Up to 8 analog inputs for voltage, current, or DC transducers, identified as 101 to
108.
D
Up to 32 digital inputs identified as 201 to 232.
E
One connector for fiber optic links. The connector has an Act indicator that lights
up when its link is active (i.e., it is receiving requests of the processing module).
RPV311
F
39