Safety Tests - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
1.11

Safety Tests

RPV311-TM-EN-7
Safety
IEC 61010-1
IEC 60255-5
Inpulse - 5KV
Dielectric withstand - 3,3KVDC for 60 seconds
Insulation > 100M Ω
Chapter 17 – Technical Specifications
Cross-over Frequency: 8.14Hz
Severity: 7.5mm zero-peak displacement below
8.14Hz
2g zero-peak acceleration above 8.14Hz
Sweep Rate: 1 Octave/minute
Number of Sweep Cycles: 1
Configuration: Operational throughout
Vertical Axis:
Frequency Range: 1Hz – 35Hz
Cross-over Frequency: 8.42Hz
Severity: 3.5mm zero-peak displacement below
8.14Hz
1g zero-peak acceleration above 8.14Hz
Sweep Rate: 1 Octave/minute
Number of Sweep Cycles: 1
Configuration: Operational throughout
Safety tests