Environmental Conditions; Type Tests Rpv311 - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 17 – Technical Specifications
1.9

Environmental Conditions

1.10

Type Tests RPV311

RPV311-TM-EN-7
Operating temperature range
Maximum operating altitude
Relative humidity
As tested per 60068-2-1
As tested per 60068-2-2
EMC tests were performed according to IEC 60255-26 referring to the following
standards
IEC 61000-4-
2:2008
IEC 61000-4-
3:2006
IEC 61000-4-
4:2012
IEC 61000-4-
5:2005
IEC 61000-4-
6:2008
IEC 61000-4-
8:2009
Environmental Conditions
- 40... +50 °C (or –13°F to +122°F)
2000 m (6560 ft)
5 ... 95 %, noncondensing
-40°C
+55°C
Type Tests RPV311
8kV contact / 15KV air (level 4)
10 V/m (level 3)
2 KV @ 5KHz (level 3)
Differential mode: 2KV
Common mode: 1KV
(level 3)
10V
30A/m continuous - 300A/m @ 1s.
RPV311
259