LG DOAS Installation And Operation Manual page 7

Dedicated outdoor air system
Table of Contents

Advertisement

REFRIGERANT SAFETY
ASHRAE Standards 15-2010 and 34-2010 offer guidelines that address refrigerant safety and the maximum allowable concentration of
refrigerant in an occupied space. Refrigerant will dissipate into the atmosphere, but a certain volume of air is required for this to occur safely.
For R410A refrigerant, the maximum allowable concentration of refrigerant is twenty-six (26) lbs. per 1,000 cubic feet of an occupied space.
Buildings with twenty-four (24) hour occupancy allow half of that concentration.
ASHRAE Standards 15 and 34 assume that if a system develops a leak, its entire refrigerant charge will dump into the area where the leak
occurs. To meet ASHRAE Standards 15 and 34, calculate the refrigerant concentration that may occur in the smallest room volume on the
system, and compare the results to the maximum allowable concentration number. Also consult state and local codes in regards to
refrigerant safety.
Verify the maximum refrigerant concentration level for spaces served by DOAS meets the concentration limit for the application.
Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arnd20bdat2Arnd20bdar2

Table of Contents