START-UP
Web System Interface
Network Page
8. Expand the Lon Comm Config property group. The Lon Comm Config group contains properties for synchronizing the timing of the Lon
driver with the timing of the network.
9. Edit any necessary Lon configurations.
10. Expand the Lon Netmgmt property group. This property group contains the Domain ID which needs to be configured based on how the
network is identified. The integration engineer needs to properly address the Lon Netmgmt properties.
Figure 61:Lon Device Properties - Comm Config and Lon Netmgmt
11. Expand the Local Lon Device property group. The Local Lon Device properties contains additional details about Lon device properties.
12. Expand the Device Data properties group. The Device Data group properties contain the Neuron Id, Program Id and Node State.
The Neuron Id and Program Id are populated by the Lon card in the controller and SHOULD NOT be changed.
13. Select Config Online from the Node State drop-down menu.
14. Ensure the Subnet Node Id matches the desired node address. The Subnet Node Id defines the node address based on the subnet and
node that were entered on the editing dialog on the Lon Device Manager tab. Each device on the network must have a unique Subnet
Node Id.
15. Select true from the Has Node Object drop-down menu.
16. If desired, enter a Location and Self Doc. These fields are used for identification purposes only.
17. Click the Save button.
Figure 62:Lon Device Data Properties
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.