8.2
New Zealand FB Silence switch (outside
switch)
NOTE! The functions in this chapter are valid for the New Zealand
convention only.
The "New Zealand FB Silence switch" is called the "outside switch"
since it is placed outside the c.i.e. The outside switch is a key switch
and connected to a programmable input with the trigger condition
"New Zealand FB Silence switch".
The outside switch can be in two states.
The outside switch is turned ON (i.e. from not activated to activated
state).
 All programmable outputs of type "Alarm devices" are
disabled, i.e. they cannotbe activated. The "inside switch" (se
above) has no function.
 LED:s "Fire" (on the front) changes from blinking to steady
29
(continuous).
 The c.i.e. built-in buzzer is silenced.
 A fault is generated
active"
.
The outside switch is turned OFF (i.e. from activated to not
activated state).
 The fault "
FAULT: FB Silence switch active"
31
Serviced
.
 Any alarm point / zone in fire alarm state will automatically be
disabled / isolated. (I.e. it has to be re-enabled via menu
H2/B5-B6.)
 Any alarm point / zone in fire alarm state will automatically
change state to "Isolated alarm" and in the fire alarm list
(presented in the LCD) will "
An example:
ISO ZONE-ADDR 12-46 LAST ZONE 12
This is a user defined alarm text.
29
This is valid also if the fire alarm is activated after the outside switch is
turned ON.
30
Always latched, regardless of if faults are programmed to be not latched.
31
Since this fault is always latched, it has to be acknowledged via menu H6.
28
EBL128 Operating Instructions V1.1.x
30
"
FAULT: FB Silence switch
:
ALM
" be changed to "
will be
ISO
".
No. 01