Co-Incidence Alarm (Two-Unit / -Zone Dependence); Heavy Smoke Alarm / Heavy Heat Alarm - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
16.2.3
16.3
time, otherwise will the output for routing equipment (Fire brigade tx)
be activated. See EBL128 Planning Instructions for more information
regarding the AA function. Acknowledgement
alarm can be done on an AA unit 1735 / 1736 (or an AA controller
1740). See also chapter "Alarm reset", page 50.

Co-incidence alarm (two-unit / -zone dependence)

When only one two-unit dependent alarm point, (i.e. one zone –
address) is in alarm status
48
zone is in alarm status
, the buzzer sounds (0.8 / 5 sec.) and there is a
Co-incidence alarm presentation in the display.
Co-incidence alarm detector ZZ/AA
or
Co-incidence alarm zone ZZ
If there are Co-incidence alarms generated in other zones, the LEDs
"Alarms queued" (L2) are blinking and the Co-incidence alarms will
be automatically scrolled (each 5
Co-incidence alarm is automatically reset 5 minutes after the alarm
point / zone is no longer in alarm status or by the Reset button (P4),
see chapter "Alarm reset", page 50.

Heavy smoke alarm / Heavy heat alarm

An analog detector generates heavy smoke / heat alarm for a higher
49
alarm level
than the fire alarm level, i.e. fire alarm is already
activated by the same detector.
Heavy smoke / heat alarm is a confirmation on that the smoke or heat
is increasing and can be used for special actions, e.g. activation of
smoke ventilation, etc.
In case of a heavy smoke / heat alarm, the following will happen:
 Outputs programmed for heavy smoke / heat alarm are
50
activated.
46
In the "Czech" and "Polish" (CNBOP) conventions, the push button
"Evacuate" (P5) can be used for "AA Acknowledge".
47
If two or more two-unit dependent alarm points (zone - addresses) in the
same zone are in alarm status at the same time, normal fire alarms will be
activated in EBL128. See also EBL128 Planning Instructions.
48
If two or more two-zone dependent zones in the same group are in alarm
status at the same time, normal fire alarms will be activated in EBL128. See
also EBL128 Planning Instructions.
49
See EBL128 Planning Instructions.
50
General heavy smoke / heat alarm and individual alarm points / zones.
46
EBL128 Operating Instructions V1.1.x
46
and reset of the AA
47
or when only one two-zone dependent
th
second).