Layout Principles - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
The layout and installation of pipes should facilitate the maintenance of the unit.
Checking Electrical Access for Auxiliaries
The modular indirect evaporative cooling system is an important air handling unit
(AHU). You need to strictly follow the heating, ventilating, and air conditioning
(HVAC) construction requirements. To ensure proper operation of the unit, protect
it against dust, dirt, corrosive gas, and high humidity.
Connection Engineering Precautions

4.1.2 Layout Principles

Install the unit strictly according to the design drawing and reserve space for
maintenance and ventilation.
Figure 4-1 Maintenance space (unit: mm)
(1) Wall
Issue 10 (2024-01-30)
NO TICE
NO TICE
Air duct installation: A flexible connector should be installed between the unit
and air duct. The air duct should not bear the weight of the unit. Install a
support for an air duct, and ensure that the joint between an air duct and the
unit is not exposed to stress.
Pipe thermal insulation: Take thermal insulation measures for all inlet pipes
and drainpipes of the unit. Reserve sufficient space for maintenance and
operations when installing thermal insulation foam for valves and connectors.
At low temperatures, take thermal insulation measures to prevent water pipes
from freezing.
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Indoor air supply vent
4 Installation Guide
(3) Electric control box
35