NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Procedure
Step 1 On the home screen, choose Settings > Alarm Settings > T/H Sensor.
Figure 11-18 Setting alarm parameters
Step 2 Tap the value next to the Threshold column of the Return air high temperature
alarm.
Figure 11-19 Setting thresholds
----End
11.3.16 How Do I Commission a Component?
Context
●
●
●
Procedure
Step 1 On the home screen, choose Maint > Diagnostic Mode > Enter to enter the
diagnostic mode.
Issue 10 (2024-01-30)
On the Diagnostic Mode screen, you can enable or disable components and
control their output ratio.
To perform manual operations on system components in diagnostic mode,
ensure that the system is powered on.
The following describes how to commission an indoor fan.