5.9 (Optional) Powering Off the Unit

Context
In shutdown mode, the Shutdown button is green (unavailable) and the Start
button is gray (available).
Procedure
Step 1 Tap Shutdown on the home screen of the display module. A warning is displayed,
indicating whether to shut down the unit.
Issue 10 (2024-01-30)
Figure 5-18 Wizard Startup
NO TE
After commissioning for a component succeeds, the system automatically performs
commissioning for the next component you selected. Please wait during the
commissioning.
Check the commissioning result.
If the message "Commissioning succeeded" is displayed in the lower left
corner, tap Confirm. The home screen is displayed.
If the message "Commissioning failed" is displayed in the lower left
corner:
i.
Click the link at "Commissioning failed" to view the failure cause, tap
Back and Confirm, and troubleshoot based on the failure cause.
ii.
On the home screen, choose Maint > Wizard Startup and perform
commissioning again.
Figure 5-19 Wizard-based startup result
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On and Commissioning
119