NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
2.
----End
5.9 (Optional) Powering Off the Unit
Context
In shutdown mode, the Shutdown button is green (unavailable) and the Start
button is gray (available).
Procedure
Step 1 Tap Shutdown on the home screen of the display module. A warning is displayed,
indicating whether to shut down the unit.
Issue 10 (2024-01-30)
Figure 5-18 Wizard Startup
NO TE
After commissioning for a component succeeds, the system automatically performs
commissioning for the next component you selected. Please wait during the
commissioning.
Check the commissioning result.
–
If the message "Commissioning succeeded" is displayed in the lower left
corner, tap Confirm. The home screen is displayed.
–
If the message "Commissioning failed" is displayed in the lower left
corner:
i.
Click the link at "Commissioning failed" to view the failure cause, tap
Back and Confirm, and troubleshoot based on the failure cause.
ii.
On the home screen, choose Maint > Wizard Startup and perform
commissioning again.
Figure 5-19 Wizard-based startup result
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On and Commissioning
119