Connecting cables to the PDU for a 1+1 or 2+0 UPS2000-G-10 kVA parallel system (three-phase input single-phase
output)
 Cable list
No.
Item
PDU AC
1
OUTPUT power
cable
PDU AC INPUT
2
power cable
UPS1 AC INPUT
3
power cable
UPS1 AC
4
OUTPUT power
cable
UPS2 AC INPUT
5
power cable
UPS2 AC
6
OUTPUT power
cable
Maintenance
7
bypass port cable
CAN
8
communications
port cable
Cable for short-
circuiting mains
9
and bypass input
N wiring terminals
Appearance
M4
11
Specifications
10 mm² (1+1
UPS2000-G-10 kVA
parallel system)
16 mm² (2+0
UPS2000-G-10 kVA
parallel system)
6 mm² (1+1 UPS2000-
G-10 kVA parallel
system)
6 mm² (2+0 UPS2000-
G-10 kVA parallel
system)
N/A
N/A
N/A
N/A
RVV 4 x 0.5
SBYV-100 4 x 2 x 0.5
M6
6 mm²
Remarks
Prepared
onsite
Prepared
onsite
The cables is
delivered with
PDU, with a
part number of
04090675.
Prepared
onsite
(connectors
provided)
Prepared
onsite
Prepared
onsite