Huawei iSitePower-M User Manual page 63

Hide thumbs Also See for iSitePower-M:
Table of Contents

Advertisement

iSitePower-M (MAP05A1, MAB05B1)
User Manual
Cable Type
Table 7-1 Cables prepared by the customer (standard scenario)
No.
Cable
1
PV input
power cable
2
AC input and
output
power cables
3
Ground cable Outdoor
4
Dry contact
signal cable
Table 7-2 Cables prepared by the customer for the AC parallel box (parallel system scenario)
No.
Cable
1
AC input power
cable from the
mains input to
the parallel box
2
Cable from the
parallel box to
the iSitePower-
M AC input
port
3
Cable from the
iSitePower-M
AC output port
to the parallel
box
Issue 02 (2021-12-30)
Type
Recommended Specifications
Common
● Conductor cross-sectional area: 4–6 mm
outdoor PV
● Cable outer diameter: 5.5–9 mm
cable in the
industry
Outdoor
● Conductor cross-sectional area: 4–6 mm
three-core
● Cable outer diameter: 13.7–16.9 mm
copper cable
(L/N/PE)
Main ground cable: 4–6 mm
single-core
cross-sectional area of the AC input power
copper cable
cable)
Ground cable between battery modules
(capacity expansion scenario): 6 mm
Outdoor
● Conductor cross-sectional area: 0.2–1 mm
shielded
● Cable outer diameter: 6.3–7.5 mm
twisted pair
cable (8
cores)
Type
Recommended Specifications
Outdoor
● Conductor cross-sectional area: 25 mm
three-core
● Cable outer diameter: 16–26 mm
copper
cable
(L/N/PE)
Outdoor
● Conductor cross-sectional area: 4–6 mm
three-core
● Cable outer diameter: 13.7–16.9 mm
copper
cable
(L/N/PE)
Outdoor
● Conductor cross-sectional area: 4–6 mm
three-core
● Cable outer diameter: 13.7–16.9 mm
copper
cable
(L/N/PE)
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Electrical Connection
2
2
2
(same as the
2
2
2
2
2
Source
Prepared
by the
customer
Prepared
by the
customer
Prepared
by the
customer
Prepared
by the
customer
Source
Prepared
by the
customer
Prepared
by the
customer
Prepared
by the
customer
58

Advertisement

Table of Contents
loading

This manual is also suitable for:

Map05a1Mab05b1

Table of Contents