II. Match BurnerID's on LMV5(Y) and LMV5(Z)
1) On AZL5(Y) go to Operation> press Enter, scroll down to BurnerID, press Enter again, and
record LMV5(Y)'s BurnerID. On AZL5(Z) go to Operation> press Enter, scroll down to
BurnerID, press Enter again, and check LMV5(Z)'s BurnerID. If it's XXXX, LMV5(Z) is blank.
If LMV5(Z) has a BurnerID, it must be changed to exactly match LMV5(Y). Go to Updating>,
enter the Service or OEM level password, scroll down to BurnerID, press Enter and modify as
needed.
III. Restore LMV5(Y) parameters to LMV5(Z)
1) Connect AZL5(Y) to the blank or BurnerID matched LMV5(Z).
Input the Service or OEM password.
Go to Updating> Parambackup >, select AZL ->LMV5x, and press Enter.
The parameter set will be transferred from AZL5(Y) to LMV5(Z).
The following text will be shown on the AZL5 during the transfer:
"Parameters being updated
"Backup Restore is carried out"
WAIT for the next line of text / step. Do not interrupt! It may take up to 5 minutes!
"Backup Restore finished Parameter BC : Complete"
"Backup Restore finished Parameter BC : Partial"
Either of the above lines indicates that the parameter set transfer from the AZL5(Y) to the
LMV5(Z) was successful and that the process is complete.
Also, it is normal to get an alarm (!) during this process.
Note: It is VERY IMPORTANT that no interruptions occur when the parameters are transferred
between the AZL5 and the LMV5. If an interruption occurs, a damaged parameter set will
result. If this happens, backup the AZL5 to the LMV5 again.
IV. Return AZL5(Y) to LMV5(Y) and AZL(Z) to LMV5(Z)
1) After this is done, put the original AZL5(Y) back on the original LMV5(Y).
Connect the AZL5(Z) to LMV(Z).
Once again go to Updating> Parambackup, but this time select LMV5x -> AZL.
Press Enter, and the parameter set will be written from LMV5(Z) to AZL5(Z).
Note: The AZL5(Z) does not need to be blank. The BurnerID in the LMV5 will overwrite it.
An LMV5 will always overwrite the BurnerID in the AZL5.
An AZL5 will never overwrite a BurnerID in an LMV5 that has a different BurnerID.
An AZL5 will write a BurnerID to a LMV5 that does not have a BurnerID.
V. Modify LMV5(Z) BurnerID
1) Change the BurnerID of LMV5(Z) to something unique, different from LMV5(Y).
The BurnerID is typically set to the burner or boiler serial number.
The OEM password is needed to access this.
Note: The BurnerID is a safety feature that identifies and matches a parameter set to a burner.
It functions as a parameter set's name. Whenever a Restore is attempted, the BurnerID is
verified in a programmed LMV5. This verification does not happen if the LMV5 is blank.
LMV5 QSG Rev 4
Cancel with ESC"