Creating a LMV5 Start-Up Report 9-3
The following steps outline the procedure for saving, viewing and printing out a start-up report
(.mdb file) to a PC.
Saving the .mdb file
1) Ensure that the ACS 450 software is open, and the PC is connected to the AZL5 at the
user, service, or OEM level. See installation and set-up 9-2 if necessary. A full report will
be saved at any password level. The report can be filtered by password level when it is
viewed.
2) Go to the ACS450 System LMV5x dropdown menu, and select Backup for offline mode.
3) The ACS450 will then read the parameters on the LMV5, and compose the report. The
status of the backup (report) will be indicated on the backup window. The backup
process may take up to 10 minutes. This report will be automatically saved in
C:\Program files\ ASC450 \ daten.
4) After the backup process is complete, go to the ACS450 System LMV5x dropdown
menu, and select Disconnect. A window will appear that asks Do you want to store
parameters for offline mode?. Since this was just done is Step 3, it is not necessary to
repeat. Click no.
5) The ACS450 is now disconnected from the LMV5, and the .mdb file is saved. Once
disconnected, the .mdb file can be viewed or printed with the ACS450 software.
Viewing and printing the .mdb file contents
6) Ensure that the ACS 450 software is open, and not connected to the LMV5. Go to the
File dropdown menu, and select Show Parameters. When this is selected a window will
appear. Select the .mdb file to be opened. The default location for the .mdb files is
C:\Program files\ ASC450 \ daten. Once the file is selected, another window will appear
for the access level. Any level can be chosen to view and print the parameter list without
needing a password. The level chosen will affect what parameters appear, so selecting
the OEM level will show all parameters available in the .mdb file. Once the access level
is selected a list of the parameters and their settings should appear.
7) Once the parameter list is visible on the screen, it can be viewed and / or printed. The
fault and lockout history can also be viewed and / or printed. To access the fault and
lockout history, go to the Parameters dropdown menu and slide the cursor to Operating
State. The options of Fault History and Lockout History should appear. Click on either to
view.
Note: Many people prefer to create the start-up report in a more universal document format,
such as a .pdf file type. This can be done with various Adobe ® software that has a
writer function. To create the .pdf files, simply print the desired pieces of the .mdb file to
the .pdf writer instead of an actual paper and toner printer. Most people prefer to .pdf
the parameter list, fault history, and lockout history. These pieces together provide a
very inclusive LMV5 start-up report.
LMV5 QSG Rev 4
Sec 9 Pg 3
www.scccombustion.com