2. Control Functions
Control of the cooling cycle
2 Protection controls
The basic control follows the contents of section 1, but the following functions are also implemented for the protection 
of the product.
a. Low pressure over-increase prevention control
In case of continued operation conditions of low pressure higher than 0.5 MPa, the valve is forced to close and 
momentarily set somewhat close in comparison with the opening under normal control.
b. Discharge gas superheat decrease prevention control
During  normal  operation  (during  suction  gas  superheat  control),  in  case  of  continued  operation  conditions  of 
discharge gas superheat temperature lower than 5ºC, the valve is forced to close and momentarily set somewhat 
close in comparison with the opening under normal operation.
c. Discharge gas temperature overheat prevention control
In case of continued operation conditions of discharge gas temperature higher than 80ºC, overheating of discharge 
gas temperature is prevented by controlling the opening so as to make discharge gas temperature become 75ºC.
d. Evaporated gas temperature decrease prevention control
In case of continued operation conditions of evaporated gas temperature (refrigerant inlet temperature of the water 
cooler) lower than -4ºC, the valve is forced to open and momentarily set somewhat open in comparison with the 
opening under normal control.
e. Forced control
In case of continued conditions of suction gas superheat higher than 8ºC, with a cold water output setting temperature 
higher than 25ºC, the valve is forced to open and momentarily set somewhat open in comparison with the opening 
under normal control.
f. 0 (zero) point adjustment control
As  a  correction  of  the  deviation  between  the  "number  of  control  pulses"  and  "number  of  actual  pulses"  of  the 
expansion  valve  opening,  generated  due  to  continuous  operation  over  a  long  period  of  time,  a  0  (zero)  point 
adjustment is performed "the first time that all compressors are stopped when more than 24 hours have passed 
since the last 0 (zero) point adjustment". In case that all compressors are not stopped at once for more than 200 
hours, then the compressors are forced to stop status (Forced thermo OFF), 0 (zero) point adjustment is performed, 
and they are restarted after a 3-minute guard. It is possible to cancel this forced 0 (zero) point adjustment from 
"Service", but it is highly encouraged to leave it "Enabled". If setting it to "Disabled", protection controls may be 
activated frequently in case of drastic variations of load.

Image diagram of basic control
Compressor
operation
start
Power ON
Standby at 0 pulses
Zero point adjustment performed upon power ON
40
SMGB0097 rev.0 - 07/2015
£ Starting control II
¢ Starting control I
Thermo OFF or stop
§ Starting control II
Superheat control
Time
Standby at 0 pulses