4. Troubleshooting
Troubleshooting by alarm code
C1-24
Alarm code
Alarm stop reason
Thermistor for detection of heat exchanger outlet (Tl) temperature indicates an abnormal value. 
PCB monitoring position
PCBd (I/O PCB) CN24 (Liquid thermistor (Tl))
N O T E
Refer thermistor characteristics chapter
C1-25
Alarm code
Alarm stop reason
Thermistor  for  detection  of  heat  exchanger  outlet  (Two2)  (rear  side  =  internal  part  of  the  heat  exchanger)  indicates  an 
abnormal value.
PCB monitoring position
PCBd (I/O PCB) CN25 (Outlet rear side thermistor (Two2))
N O T E
Refer thermistor characteristics chapter
108
SMGB0097 rev.0 - 07/2015
Liquid THM abnormality (CN24)
The connection and 
insertion of connector
CN24 on PCBd (I/O PCB) 
are correct
Yes
Remove he 
connectors and
measure thermistor resistance. 
Is resistance value
normal?
Yes
Outlet rear side THM abnormality (CN25)
The connection and 
insertion of connector
CN25 on PCBd (I/O PCB) 
are correct
Yes
Remove the 
connectors and
measure thermistor resistance. 
Is resistance value
normal?
Yes
No
Correction of connections
No
Replace thermistor
Replace PCBd (I/O PCB) 
No
Correction of connections
No
Replace thermistor
Replace PCBd (I/O PCB) 