2. Control Functions
Control functions on the module
2 Mode II
Mode II is used mainly for systems containing multiple chiller units, or those with variable flow. To avoid alteration of the 
water temperature of the rest of chiller units in operation, the pump is operated with a low water temperature.
a. When outdoor temperature is under 2ºC
When outdoor temperature falls under 2ºC, the operation order of the pump is output, and the continuous operation 
of the cold water circulation pump starts automatically. Here, when cold water temperature becomes higher than 
5ºC, operation becomes intermittent, with the pump running for 5 minutes, then stopped during 55 minutes. 
When cold water temperature rises even further, above 7ºC, the pump operation order output is set to OFF.
b. Automatic release of anti-freezing operation
This operation is released when outdoor temperature becomes higher than 4ºC.
7
5
3
2
(a) When outdoor temperature is decreasing
Explanation diagram of automatic operation control of the pump to prevent freezing in winter (Mode II)
N O T E
When the outdoor temperature of the cold water circulation system is lower than that of the installation place of the
chiller unit itself, then it is necessary to install a separate outdoor temperature thermostat in the place with the lowest
temperature, and connect it in parallel with the operation order circuit of the pump.
18
SMGB0097 rev.0 - 07/2015
Secondary
pump
7
More than
Less than
5
More than
Less than
3
More than
Less than
4
(b) When outdoor temperature is increasing
Load
Chiller 
unit
Chiller 
unit
Primary pump
More than
Less than
More than
Less than
More than
Less than
2
4
Explanation of codes
Continuous pump operation
Intermitent pump operation
5 minutes run
55 minutes stop
× Pump stop
→    C hange trend of cold water 
temperature