3.1.2

Environmental Conditions

Avoid installing the L3 controller in any location where:
• the ambient temperature can fall out of the range between 0
• the relative humidity can fall out of the range between 20% and 90%;
• condensation can occur due to rapid temperature change;
• equipment can be exposed to vibrations exceeding the allowable limit;
• equipment can be exposed to the impact exceeding the allowable limit;
• there is corrosive gas or flammable gas (sulfur dioxide content must be 0.05 ppm or
less, and hydrogen sulfide content be 0.01 ppm or less);
• there is dust (the amount of dust must not exceed 0.1 mg/m
particles;
• the equipment is exposed to direct sunlight.
• Do not use the L3 controller under any environment condition given above. Malfunction or
failure can be caused.
• Do not use the L3 controller when alarm signal is generated due to internal temperature rise.
Malfunction, failure, smoking or fire can be caused.
When installing a console in which the L3 controller is mounted, observe the following.
• Install the console away as far from a high-voltage panel or power panel as possible.
• When there is a high-frequency device or facility nearby, ground the console properly.
If it is necessary to use a transceiver etc., use it with 1 W or lower power, at a position
1 m or more away from the L3 controller.
• If the channel base is shared with other panels, confirm that there is no leak current
from other panels or the L3 controller.
3.1.3

Power Supply Equipment

To ensure stable operation of the system, high-quality power supply is essential.
Power conditions (AC)
Rated voltage: 100/200 Vac
Frequency: 50/60 Hz
Distortion rate: 5% or less
Power requirement: 175 W or less
Allowable instantaneous interruption: 20 ms min.
Power conditions (DC)
Rated voltage: 24 Vdc
Ripple: 2% or less
Allowable instantaneous interruption: 1 ms
6F8C0882
CAUTION
±
1 Hz
3.1 Installation Environment
o
o
C and 55
C;
3
), sodium, or iron