Particulate Contamination

94
G8264 Installation Guide
Attention: Airborne particulates (including metal flakes or particles) and reactive 
gases acting alone or in combination with other environmental factors such as 
humidity or temperature might pose a risk to the device that is described in this 
document.
Risks that are posed by the presence of excessive particulate levels or concentrations 
of harmful gases include damage that might cause the device to malfunction or 
cease functioning altogether. This specification sets forth limits for particulates and 
gases that are intended to avoid such damage. The limits must not be viewed or 
used as definitive limits, because numerous other factors, such as temperature or 
moisture content of the air, can influence the impact of particulates or 
environmental corrosives and gaseous contaminant transfer. In the absence of 
specific limits that are set forth in this document, you must implement practices that 
maintain particulate and gas levels that are consistent with the protection of human 
health and safety. If Lenovo determines that the levels of particulates or gases in 
your environment have caused damage to the device, Lenovo may condition 
provision of repair or replacement of devices or parts on implementation of 
appropriate remedial measures to mitigate such environmental contamination. 
Implementation of such remedial measures is a customer responsibility.
Contaminant
Limits
Particulate
• The room air must be continuously filtered with 40% atmo‐
spheric dust spot efficiency (MERV 9) according to ASHRAE 
Standard 52.21.
• Air that enters a data center must be filtered to 99.97% efficiency 
or greater, using high‐efficiency particulate air (HEPA) filters 
that meet MIL‐STD‐282.
• The deliquescent relative humidity of the particulate contami‐
nation must be more than 60%2.
• The room must be free of conductive contamination such as zinc 
whiskers.
Gaseous
• Copper: Class G1 as per ANSI/ISA 71.04‐19853
• Silver: Corrosion rate of less than 300 Å in 30 days
ASHRAE 52.2‐2008 ‐ Method of Testing General Ventilation Air‐Cleaning Devices for 
Removal Efficiency by Particle Size. Atlanta: American Society of Heating, 
Refrigerating and Air‐Conditioning Engineers, Inc.
The deliquescent relative humidity of particulate contamination is the relative 
humidity at which the dust absorbs enough water to become wet and promote 
ionic conduction.
ANSI/ISA‐71.04‐1985. Environmental conditions for process measurement and control 
systems: Airborne contaminants. Instrument Society of America, Research Triangle 
Park, North Carolina, U.S.A.