Configuration for 600VAC Single Phase System

Grid 1 or Grid 2 Tab
GFK-2749
The following shows a typical hardware configuration for a signal phase, 3-wire power
monitoring application. This example shows settings for Grid 1; all the settings can be
applied to the respective Grid 2 parameters. Empirical measurement showed that the
system runs, nominally, around 595VAC RMS with a maximum load, after the CT ratio, of
3.7A RMS. The offset and gain values are shown at their default values. For maximum
accuracy, the offset and gain values must be set, based on the IC694PSM001 module
faceplate label and on the IC694ACC200 terminal assembly label calibration constants.
Note that the 600V range will accurately measure voltages to slightly above 690VAC
RMS. The Nominal Voltage is the anticipated Phase-to-Neutral voltage in the single phase
configuration.