3
%Q Configuration Values
3-46
This table shows the settings for both grids. These bits must be set during the first PLC
scan when the PLC transitions to run mode. %Q offset 2, 3 & 4 and 18, 19 & 20 set the
PSM for the field voltage and power configuration. Setting these values incorrectly will
yield invalid readings. All remaining bits may be changed during run mode to adapt to
changing field conditions.
%Q Bit
Function
Offset
1
GRID 1 Operation
2
GRID 1 Voltage Selection
3
GRID 1 Grid Operational Mode
4
GRID 1 Connection mode
5
GRID 1 PTA_CA measurement
6
GRID 1 CTA measurement
7
GRID 1 PTB measurement
8
GRID 1 CTB measurement
9
GRID 1 PTC measurement
10
GRID 1 CTC measurement
11
GRID 1 CTN measurement
12
GRID 1 Waveform Capture
13
GRID 1 Delta Mode
14
Reserved
15
GRID 1 Energy reset
16
Relay open
17
GRID 2 Operation
18
GRID 2 Voltage Selection
19
GRID 2 Grid Operational Mode
20
GRID 2 Connection mode
21
GRID 2 PTA_CA measurement
22
GRID 2 CTA measurement
23
GRID 2 PTB measurement
24
GRID 2 CTB measurement
25
GRID 2 PTC measurement
26
GRID 2 CTC measurement
27
GRID 2 CTN measurement
28
GRID 2 Waveform Capture
29
GRID 2 Delta Mode
30
Reserved
31
GRID 2 Energy reset
32
Relay close
PACSystems* RX3i Power Sync and Measurement System – February 2013
Value
Comment
1
Enable grid 1
1
600VAC range
1
3-phase
0
4-wire, Wye power system
1
VA1 measurement is on
1
IA1 measurement is on
1
VB1 measurement is on
1
IB1 measurement is on
1
VC1 measurement is on
1
IC1 measurement is on
1
IN1 measurement is on
0
Set this to capture a waveform
0
Delta Mode only affects Delta
configurations
0
Always zero
0
Set this to reset Energy value to Zero
1
Clear this bit (AND set bit 32) to
request synchronizing the Grids
1
Enable grid 1
1
600VAC range
1
3-phase
0
4-wire, Wye power system
1
VA2 measurement is on
1
IA2 measurement is on
1
VB2 measurement is on
1
IB2 measurement is on
1
VC2 measurement is on
1
IC2 measurement is on
1
IN2 measurement is off
0
Set this to capture a waveform
0
Delta Mode only affects Delta
configurations
0
Always zero
0
Set this to reset Energy value to Zero
0
Set this bit (AND clear bit 16) to
request synchronizing the Grids