Parameters Sent To Psm Module - GE PACSystems RX3i User Manual

Power sync and measurement system
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

3

Parameters sent to PSM Module

Index
(%AQ Word 1)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
22
23
26
26
27
3-22
Many of the configuration parameters can be modified by the application logic during
runtime. These parameters are set initially when the hardware configuration is
downloaded, but can be modified during runtime to adjust to changing conditions.
Parameters are changed using two Word Parameter Write registers in %AQ memory. The
first word contains the parameter index number and the second word contains the
parameter value. One parameter can be changed per RX3i controller scan. Both %AQ
locations should be set to a value of 0 when parameter values are not being changed.
It is recommended that the %AQ Word 2 be set to the desired value first, followed by the
%AQ Word 1 being set to the index for at least one PLC scan. Then the %AQ Word 1
should be set to zero, followed by the %AQ Word being set to zero.
Parameter Value
(%AQ Word 2)
GRID 1 MODULE OFFSET
GRID 1 MODULE GAIN
GRID 1 VA1 GAIN LOW
GRID 1 VA1 GAIN HIGH
GRID 1 IA1GAIN
GRID 1 VB1 GAIN LOW
GRID 1 VB1 GAIN HIGH
GRID 1 IB1 GAIN
GRID 1 VC1 GAIN LOW
GRID 1 VC1 GAIN HIGH
GRID 1 IC1 GAIN
GRID 1 IN1 GAIN
GRID 1 Nominal Voltage
GRID 1 Nominal Current
GRID 1 Nominal Frequency
GRID 2 MODULE OFFSET
GRID 2 MODULE GAIN
GRID 2 VA2 GAIN LOW
GRID 2 VA2 GAIN LOW
GRID 2 IA2 GAIN
GRID 2 VB2 GAIN LOW
GRID 2 VB2 GAIN HIGH
GRID 2 IB2 GAIN
GRID 2 VC2 GAIN LOW
GRID 2 VC2 GAIN HIGH
GRID 2 IC2 GAIN
GRID 2 IN2 GAIN
5
A negative value of the Grid 1 or Grid 2 nominal current (Parameter # 14 or #29) means that
the Grid's total active power under normal conditions is expected to have a negative sign. The
user is responsible for the correct PT/CT connections to get the negative sign for the active
power of each phase.
PACSystems* RX3i Power Sync and Measurement System – February 2013
Default value
0
Calibrated value, -1000 to +1000
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
1200 [0.1 V]
450 to 1500 or 1200 to 7500
5000 [0.001 A]
-7500 to 7500
6000 [0.01 Hz]
5000 or 6000
0
Calibrated value, -1000 to +1000
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
0x4000
Calibrated value, 0h to FFFFh
Value Limits
5
GFK-2749