System Configuration Mismatch (Group 11) - GE PACSystems RX7i Cpu Programmer's Reference Manual

Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

9.4.6

System Configuration Mismatch (Group 11)

The fault group Configuration Mismatch occurs when the module occupying a slot is different from
that specified in the configuration file. When the GBC generates the mismatch because of a Genius
block, the second byte in the Fault Extra Data field contains the bus address of the mismatched
block.
Default action: Fatal. Configurable.
Note: If a system configuration mismatch occurs when the CPU is in RUN Mode, the fault action will
be Diagnostic regardless of the fault configuration. See Fault Parameters in PACSystems
RX7i, RX3i and RSTi-EP CPU Reference Manual, GFK-2222.
2, Genius I/O Block Model Number Mismatch
The CPU generates this fault when the configured and physical Genius I/O blocks have different
model numbers.
Correction
1) Replace the Genius I/O block with one corresponding to the configured module.
2) Update the configuration file.
Fault Extra Data for Genius I/O Block Model Number Mismatch
Byte
Value
[0]
FF (flag byte)
[1]
Serial Bus address
[2]
Installed module type (refer to Installed/Configured Module Types (Bytes 2 and 3 of Fault
Extra Data) below).
[3]
Configured module type (refer to Installed/Configured Module Types (Bytes 2 and 3 of Fault
Extra Data) below).
Installed/Configured Module Types (Bytes 2 and 3 of Fault Extra Data)
Number
Decimal Hexadecimal
4
4
5
5
6
6
7
7
8
8
9
9
10
A
11
B
12
C
13
D
32
20
69
45
70
46
70
46
71
47
GFK-2950C
Description
Genius Network Interface (GENI)
Phase B Hand Held Monitor
Phase B Series Six GBC with Diagnostics
Phase B Series Six GBC without Diagnostics
PLCM/Series Six
PLCM/Series 90-70
Series 90-70 Single Channel Bus Controller
Series 90-70 Dual Channel Bus Controller
Series 90-10 Genius Communications Module
Series 90-30 Genius Communications Module
High Speed Counter
Phase B 115Vac 8-point (2 amp) Grouped Block
Phase B 115Vac/125Vdc 8-point Isolated Block
Phase B 115Vac/125Vdc 8-point Isolated Block without Failed Switch
Phase B 220Vac 8-point Grouped Block
February 2018
Chapter 9. Diagnostics
401