GE AF-650 GP Programming Manual page 50

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
Stop [RPM]. The motor is running and there
are no warnings.
[7]
Run in
Motor is running within the programmed
range / no
current and speed ranges set in
warning
parameter H-70 Warning Current Low to
parameter H-73 Warning Speed High. There
are no warnings.
[8]
Run on
Motor runs at reference speed.
reference / no
warning
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
An alarm or a warning activates the
warning
output.
[11]
At torque
The torque limit set in
limit
parameter F-40 Torque Limiter (Driving) or
F-41 has been exceeded.
[12]
Out of current
The motor current is outside the range set
range
in parameter F-43 Current Limit.
[13]
Below current,
Motor current is lower than set in
low
parameter H-70 Warning Current Low.
[14]
Above
Motor current is higher than set in
current, high
parameter H-71 Warning Current High.
[15]
Out of range
Output frequency is outside the frequency
range set in parameter H-70 Warning
Current Low and parameter H-71 Warning
Current High.
[16]
Below speed,
Output speed is lower than the setting in
low
parameter H-72 Warning Speed Low.
[17]
Above speed,
Output speed is higher than the setting in
high
parameter H-73 Warning Speed High.
[18]
Out of
Feedback is outside the range set in
feedback
parameter H-76 Warning Feedback Low and
range
parameter H-77 Warning Feedback High.
[19]
Below
Feedback is below the limit set in
feedback low
parameter H-76 Warning Feedback Low.
[20]
Above
Feedback is above the limit set in
feedback high
parameter H-77 Warning Feedback High.
[21]
Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[22]
Ready, no
Frequency converter is ready for operation
thermal
and there is no over-temperature warning.
warning
[23]
Remote,
Frequency converter is ready for operation
ready, no
and is in Auto mode. There is no over-
thermal
temperature warning.
warning
[24]
Ready, no
Frequency converter is ready for operation
over-/ under
and the mains voltage is within the
voltage
specified voltage range (see General Specifi-
cations section in the relevant Design
Guide).
[25]
Reverse
Reversing. Logic '1' when CW rotation of
the motor. Logic '0' when CCW rotation of
DET-618D
AF-650 GP™ Programming Guide
[26]
Bus OK
[27]
Torque limit
and stop
[28]
Brake, no
brake warning
[29]
Brake ready,
no fault
[30]
Brake fault
(IGBT)
[31]
Relay 123
[32]
Mechanical
brake control
[40]
Out of ref
range
[41]
Below
reference low
[42]
Above
reference high
[45]
Bus Ctrl
[46]
Bus Ctrl On at
timeout
[47]
Bus Ctrl Off at
timeout
[55]
Pulse output
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
02/2016 All rights reserved.
the motor. If the motor is not rotating the
output will follow the reference.
Active communication (no time-out) via
the serial communication port.
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and is
at the torque limit, the signal is Logic '0' .
Brake is active and there are no warnings.
Brake is ready for operation and there are
no faults.
Output is Logic '1' when the brake IGBT is
short-circuited. Use this function to protect
the frequency converter if there is a fault
on the brake modules. Use the output/
relay to cut out the main voltage from the
frequency converter.
Relay is activated when Control Word [0] is
selected in parameter group O-##.
Enables control of an external mechanical
brake, see description in parameter group
B-2# Mechanical Brake.
Active when the actual speed is outside
settings in parameter H-72 to H-75.
Active when actual speed is below speed
reference setting.
Active when actual speed is above speed
reference setting.
Controls output via bus. The state of the
output is set in parameter E-90 Digital &
Relay Bus Control. The output state is
retained in the event of bus time-out.
Controls output via bus. The state of the
output is set in parameter E-90 Digital &
Relay Bus Control. In the event of bus time-
out the output state is set high (On).
Controls output via bus. The state of the
output is set in parameter E-90 Digital &
Relay Bus Control. In the event of bus time-
out the output state is set low (Off).
See parameter group LC-1#. If Comparator
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-1#. If Comparator
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-1#. If Comparator
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-1#. If Comparator
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
3
3
49