Parameter Descriptions

3.17 ID-## Drive Information

Parameter group related to drive information such as
operating data, hardware configuration and software
version.
3.17.1 ID-0# Operating Data
Parameters to view operating hours. kWh counters, power
ups, etc.
ID-00 Operating hours
Range:
Function:
0 h
[0 - 2147483647 h] View how many hours the frequency
*
converter has run. The value is saved
when the frequency converter is
turned off.
ID-01 Running Hours
Range:
Function:
0 h
[0 -
View how many hours the motor has run.
*
2147483647 h]
Reset the counter in
parameter ID-07 Reset Running Hours
Counter. The value is saved when the
frequency converter is turned off.
ID-02 kWh Counter
Range:
Function:
0 kWh
[0 -
Registers the power consumption of
*
2147483647
the motor as an average value over 1
kWh]
hour. Reset the counter in
parameter ID-06 Reset kWh Counter.
ID-03 Power Up's
Range:
Function:
0
[0 - 2147483647] View the number of times the frequency
*
converter has been powered up.
ID-04 Over Temp's
Range:
Function:
0
[0 - 65535] View the number of frequency converter
*
temperature faults.
ID-05 Over Volt's
Range:
Function:
0
[0 - 65535] View the number of frequency converter
*
overvoltages.
ID-06 Reset kWh Counter
Option:
Function:
[0]
Do not reset
No reset of the kWh counter is required.
*
[1]
Reset counter Press [OK] to reset the kWh counter to 0
(see parameter ID-02 kWh Counter).
DET-618D
AF-650 GP™ Programming Guide
ID-07 Reset Running Hours Counter
Option:
[0]
Do not
*
reset
[1]
Reset
counter
3.17.2 ID-1# Data Trending Settings
Data Log Settings enables continous logging of up to 4
data sources (parameter ID-10 Trending Source) at individual
rates (parameter ID-11 Trending Interval). A trigger event
(parameter ID-12 Trigger Event) and window
(parameter ID-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
ID-10 Trending Source
Option:
[0]
*
[515]
[1200] Control Word
[1201] Reference [Unit]
[1202] Reference %
[1203] Status Word
[1210] Power [kW]
[1211] Power [hp]
[1212] Torque [Nm]
[1213] Frequency
[1214] Motor current
[1217] Speed [RPM]
[1218] Motor Thermal
[1221] Torque [%] High Res.
[1222] Torque [%]
[1224] Calibrated Stator Resistance
[1225] Torque [Nm] High
[1230] DC Link Voltage
[1232] Brake Energy /s
[1233] Brake Energy Average
[1234] Heatsink Temp.
[1235] Drive Thermal
[1248] Speed Ref. After Ramp [RPM]
[1250] External Reference
[1251] Pulse Reference
[1252] Feedback[Unit]
[1257] Feedback [RPM]
[1260] Digital Input
[1262] Analog Input 53
02/2016 All rights reserved.
Function:
To reset the running hours counter to 0, select
[1] Reset and press [OK] (see
parameter ID-01 Running Hours). This
parameter cannot be selected via the serial
port, RS485.
Select [0] Do not reset if no reset of the
running-hours counter is required.
None
Readout: Actual Set-up
3
Function:
Select which variables
are to be logged.
123