Acceptance test and acceptance report
10.5 Acceptance tests
No.
r9720.0 = 1 (STO deselected)
•
r9722.0 = 0 (STO inactive)
•
•
r0046.0 = 1 (drive in "switch-on inhibit" state)
4.
Acknowledge "switch-on inhibit" and run the drive. Ensure that the correct drive is running.
The following is tested:
Correct DRIVE-CLiQ wiring between Control Unit and Motor/Power Modules
•
Correct assignment of drive No. – Motor/Power Module – motor
•
The hardware is functioning properly
•
Correct parameterization of the STO function
•
Forced Checking Procedure of the Shutdown Paths
•
272
Description
Status
Safety Integrated
Function Manual, 05/2010, A5E03264275A