7.2.2

Safety information

Risk of electric shock. A hazardous voltage is present for up to 5 minutes after the power
supply has been disconnected.
This time must elapse before any work may be carried-out on the adapter (e.g.
mounting/installation).
When opening the protective cover for the DC link, you must activate the release.
A suitable tool (e.g. screwdriver) must be used for this purpose.
The components must only be operated when the protective cover of the DC link is closed.
Damaged components must not be used further, as this could result in secondary damage
or accidents.
It is only permissible to establish connections to the DC link using the adapters that
SIEMENS has recommended (DC link adapter and DC link rectifier adapter).
Components for which the recesses for the DC link rectifier adapter have been removed
must no longer be operated without them. If components need to be operated without the
recess and without DC link rectifier adapter, the DC link cover must be replaced.
The DC link discharge voltage hazard warning on the components on which the adapter is
installed must be in the local language.
A set of labels in 16 languages is supplied with the component.
CAUTION
The screw tightening torque (1.8 Nm, tolerance +30 %) for securing components to the
module-side DC link busbar must be checked before commissioning to ensure that it is
correct. After transportation, the screws must be tightened.
If a 50 mm wide module or if a DC link component with the appropriate width (e.g. Braking
Module, Control Supply Module, Voltage Clamping Module) is located at the lefthand end of
the drive line-up, then the DC link bridge including all of the screws must be removed. It is
not permissible to insert the screws without a DC link bridge.
For all other power units and DC link components (e.g. Capacitor Module) that are wider
than 50 mm, it is not permissible to remove the DC link bridge.
If this is not carefully observed, this can result in damage and accidents.
Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
DANGER
DANGER
DANGER
DANGER
DANGER
Accessories
7.2 DC link rectifier adapter
391