Line Modules Booksize
3.4 Basic Line Modules with internal air cooling
Remove the holder for securing the Control Unit.
The plastic retaining element must be removed due to the different expansion variants:
● If the component to be installed comes into contact with the left-hand cabinet panel
● using center feed via the Basic Line Module
Use suitable tools to lift the latching device
and push up the holder
Replacing the fan for capacitor cooling of a 100 kW Basic Line Module
Before replacing the fan, you must switch off the power supplies (24 V DC and 400 V AC).
Risk of electric shock. Dangerous voltages are still present for up to 5 minutes after the
power supply has been switched off. The device cover must not be opened until this time
has elapsed.
NOTICE
When replacing the fan, you must observe the ESD regulations.
Parts must only be replaced by trained personnel (danger of damage to sensitive
components due to static electricity)!
204
Remove the holder
DANGER
After the removing the holder
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Booksize Power Units