207433
<location>Drive: Closed-loop control with encoder is not possible as the encoder has
not been unparked
Message value:
%1
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The changeover to closed-loop control with encoder is not possible as the encoder has not been unparked.
Remedy:
- check whether the encoder firmware supports the "parking" function (r0481.6 = 1).
- upgrade the firmware.
Note:
For long-stator motors (p3870.0 = 1), the following applies:
The encoder must have completed the unparking procedure (r3875.0 = 1) before a changeover can be made to
closed-loop control with encoder. The encoder is unparked with a 0/1 edge at BI: p3876 and remains unparked until
a 0 signal is again present.
207434
<location>Drive: It is not possible to change the direction of rotation with the pulses
enabled
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A drive data set was selected - with the pulses enabled - which has a different parameterized direction of rotation
(p1821).
It is only possible to change the motor direction of rotation using p1821 when the pulses are inhibited.
Remedy:
- change over the drive data set with the pulses inhibited.
- ensure that the changeover to a drive data set does not result in the motor direction of rotation being changed (i.e.
for these drive data sets, the same value must be in p1821).
See also: p1821 (Dir of rot)
207500
<location>Drive: Power unit data set PDS not configured
Message value:
Drive data set: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Only for controlled line supply infeed/regenerative feedback units:
The power unit data set was not configured - this means that a data set number was not entered into the drive data set.
Fault value (r0949, interpret decimal):
Drive data set number of p0185.
Remedy:
The index of the power unit data set associated with the drive data set should be entered into p0185.
652
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0