Block %2 Program %3 Program-Specific Start Disable Has Been Set; Block %2 Invalid Program Name %3; Block %2 Write Command Writes In Temporary Memory Area In /_N_Ext_Dir - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Read out the part program, modify it with a text editor (e.g., insert blanks or comments before the displayed block), so
that after reading it in again the part program has a different structure in the memory.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
14005
[Channel %1: ] Block %2 program %3 program-specific start disable has been set
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Program name
Definitions:
Program %3 cannot be executed, as the program-specific start disable has been set for this file.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Reset the program-specific start disable for file %3.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
14006
[Channel %1: ] Block %2 invalid program name %3
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Program name
Definitions:
When selecting or calling an NC program it was found that the program name did not follow NC conventions:
- The length of the program name, without prefix _N_ and Suffix _MPF / _SPF, must not exceed 24 characters, as
otherwise the program name is truncated in the OPI variables.
Reaction:
Alarm display.
Remedy:
- Shorten the name of the program.
- Suppress the alarm with MD 11415 $MN_SUPPRESS_ALARM_MASK_2 bit 9.
Program
Clear alarm with the Delete key or NC START.
Continuation:
14008
[Channel %1: ] Block %2 WRITE command writes in the temporary memory area in /
_N_EXT_DIR
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
A workpiece is executed from an external data register (Execute from external drives function). The part programs are
temporarily stored in the NCK directory /_N_EXT_DIR. An attempt is now made to write in this temporary directory
with a WRITE command.
The alarm is intended to indicate that this data is not stored in the original directory on the external data carrier, and
will be lost at the next part program selection because the programs in the directory /_N_EXT_DIR will then be deleted.
Reaction:
Alarm display.
Remedy:
State a directory that remains permanently loaded in the NCK as the target for the WRITE command (e.g. MPF_DIR).
The alarm can be suppressed with MD11415 $MN_SUPPRESS_ALARM_MASK_2 bit 8.
Program
Clear alarm with the Delete key or NC START.
Continuation:
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms
141