Using Point Faults; Using Alarm Contacts - GE PACSystems RX7i Cpu Programmer's Reference Manual

Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

Chapter 9. Diagnostics
9.3.3

Using Point Faults

Point faults pertain to external I/O faults, although they are also set due to the failure of associated
higher-level internal hardware (for example, IOC failure or loss of a rack). To use point faults, they
must be enabled in Hardware Configuration on the Memory parameters tab of the CPU.
When enabled, a bit for each discrete I/O point and a byte for each analog I/O channel are allocated
in CPU memory. The CPU memory used for point faults is included in the total reference table
memory size. The FAULT and NOFLT contacts, described in Using Alarm Contacts, provide access to
the point faults.
The full support of point fault contacts depends on the capability of the I/O module. Some Series 90-
30 modules do not support point fault contacts. The point fault contacts for these modules remain
all off, unless a Loss of I/O Module occurs, in which case the RX3i CPU turns on all point fault contacts
associated with the lost module.
9.3.4

Using Alarm Contacts

High (-[HA]-) and low (-[LA]-) alarm contacts are used to represent the state of the analog input
module comparator function. To use alarm contacts, point faults must first be enabled in Hardware
Configuration on the Memory parameters tab of the CPU.
The following example logic uses both high and low alarm contacts.
Note: HA and LA contacts do not create an entry in a fault table.
396
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
GFK-2950C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pacsystems rx3iPacsystems rsti-ep

Table of Contents