Error No.
Description
Total indoor unit
capacity exceeds
512
allowable heat
recovery unit
branch capacity
Master: 512
(Heat Recovery
Systems only).

Error No. 51(2) (for Heat Recovery Systems only)

Details
Value of total indoor unit capacity
exceeds allowable heat recovery
unit branch capacity specifica-
tions. After auto-pipe detection
is complete, wait 5 minutes, then
verify connected capacity.
Total indoor unit capacity is
>54,000 Btu/h for each heat
recovery unit branch pipe.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
ERROR CODES
1. Heat recovery unit port addresses are all unique, then
total indoor unit capacity is >54,000 Btu/h per each heat
recovery unit branch pipe.
2. Total indoor units connected to each heat recovery unit
branch pipe is > eight (8).
3. If 2 heat recovery unit port addresses are the same and
the ports are twinned; >108 Mbh total of multiple indoor
units are connected.
4. If 3 heat recovery unit port addresses are the same and
the ports are all connected, >162 Mbh total of multiple
indoor units connected.
5. If the total connected indoor unit nominal capacity ex-
ceeds 192 Mbh for a single heat recovery unit.
6. Wrong transmission cable / piping connections.
7. Outdoor unit and heat recovery unit PCB is defective.