Error No. 09 - LG Multi V5 Service Manual

Hide thumbs Also See for Multi V5:
Table of Contents

Advertisement

Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
WARNING
troubleshooting of the Multi V product.
Error No.
09
Indoor unit EEPROM error.
Replace the indoor unit PCB, perform the Auto Addressing procedure, and input the central control address.
Description
• Serial number on
EEPROM of indoor
unit is 0 or FFFFFF.
• Communication error
between MICOM and
EEPROM.
• Indoor unit PCB EE-
PROM is in error or
data is not available.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Details
1. Error developed in transmission between the microproces-
sor and the EEPROM on the indoor unit PCB.
2. EEPROM is damaged.
ERROR CODES

Error No. 09

Causes
141