7.5.3.5
Technical data
Safe Brake Relay
Power supply voltage
Max. permissible current drain
of the motor brake
Max. current requirements
(at 24 V DC)
Max. cross-section that can be
connected
Weight, approx.
Equipment Manual AC Drive
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0
Supplementary system components and encoder system integration
20.4 ... 28.8 V DC
Recommended nominal value of the power supply voltage 26 V DC
(to equalize and compensate for the voltage drop along the feeder
cable to the 24 V DC solenoid of the motor brake)
2 A
0.3 A + the current drain of the motor brake
2.5 mm
2
0.17 kg
7.5 Option modules, brake control